Grace Engineered Voltage Indicators

Grace Engineered Voltage Indicators

December 02, 2016
Grace Engineered Voltage Indicators

Catalog Numbers: R-3W / R-3W-SR

SafeSide thru-door voltage indicators provide electrical safety information while the panel doors are safely closed. This “one-size-fits-all” solution detects 3-phase AC or DC voltage from 40-750VAC/30-1000VDC. The encapsulated construction and redundant circuit design means rugged reliability. SafeSide products are available with flashing LEDs (R-3W) and non-flashing LEDs (R-3W-SR).

Safer Lock-Out Tag-Out (LOTO):

Keeping personnel away from live voltage is foundational to electrical safety. Electrical safety demands a precise answer to the question ‘Is voltage present?’. Thru-door voltage indicators provide visibility of voltage from outside the enclosure without exposing personnel to voltage.

More Productivity in Mechanical LOTO:

Workers performing mechanical LOTO must isolate electrical energy. An externally-mounted voltage detector provides a means to check voltage inside an electrical panel. Without a voltage indicator, a mechanic performing mechanical LOTO would be required to work in tandem with an electrician using a voltmeter to physically verify voltage inside an electrical panel. In this case, the electrician is exposed to voltage. With thru-door voltage detectors, the mechanic can verify zero electrical energy without any exposure to voltage.

Reduced Voltage Exposure and Arc Flash Risk:

Voltage is the common denominator in an electrical accident or an arc flash; no voltage means no accident, no arc flash. While performing electrical LOTO with a thru-door voltage detector installed, the electrician can pre-check the internal voltage state without opening the enclosure. Next, the electrician should replicate a zero voltage reading with his voltmeter as per NFPA 70e 120.1(5). This low-cost, redundant voltage-verification task reduces arc flash risk and increases electrical safety for workers.

Voltage Indicator With Solid-On LEDs Or Flashing LEDs

Features: 

  • Redundant Circuitry / Long Life LED’s
  • 40-750VAC / 30-1000VDC / 35-600VAC 1Ø
  • Potted Construction with 6′ Leads
  • Phase Insensitive
  • 30mm Pushbutton or Pilot Hole
  • High Surge Immunity
  • UL Listed, Type 4X, 12, 13

Applications

  • Circuit Breaker Disconnects – No Visible Blades
  • igh Energy Panels (NFPA 70E Category 3 or 4
  • Frequently Accessed Panels
  • Mechanical LOTO: Indicating Zero Energy
  • Panels with Multiple Power Sources

Three Phase 40-750VAC/30-1000VDC UL-Listed Voltage Indicator for Type 4X/12/13 for 30mm Mounting

R-3W Flashing
R-3W-KB1 Flush Mount Assembly with Bezel and R-3W (UL)
R-3W-L Adhesive-Backed Warning Label (slips over installed R-3W)
R-3W-KB-L Adhesive-Backed Warning Label (slips over installed R-3W-KB)
R-3W-SR2 Non-Flashing
R-3W-SR-KB1 Flush Mount Assembly with Bezel and R-3W-SR (UL)
R-3W-SR-L Adhesive-Backed Warning Label (slips over installed R-3W-SR)
R-3W-KB-L Adhesive-Backed Warning Label (slips over installed R-3W-SR-KB)
R-3W23 Hazardous Location Flashing Voltage Indicator
R-3W2-KB1 Flush Mount Assembly with Bezel and R-3W2 (UL)
R-3W-L Adhesive-Backed Warning Label (slips over installed R-3W2)
R-3W-KB-L Adhesive-Backed Warning Label (slips over installed R-3W2-KB)

Voltage Indicator

Typical Configuration

OPERATIONAL RANGE AC Single or 3-Phase: 40-750V 50/60Hz Operates up to 400 Hz
DC OR STORED ENERGY 30 to 1000 VDC
MAXIMUM VOLTAGE 750VAC/1000VDC – Surge 4300V for 5 seconds
POWER CONSUMPTION 1.2 Watts @ 750 VAC (Approximately)
TEMPERATURES Operate: -20ºC to +55ºC, Storage: -45ºC to +85ºC
FAILURE CURRENT Maximum single component failure fault current is 3.7mA @ 750 3-Phase
FUSING Follow all Local, State, and national Electrical Codes when installing this equipment. Overcurrent protection of the supply leads may be necessary. The installation of overcurrent protection shall be in accordance with the requirements in the NEC (NFPA 70) or end product standard(s) when used in the final installation.

 

3-PHASE LINE-TO-LINE <29 30 120 240 480 600 750
FLASHES/SEC (TYPICAL) 0 1.3 4.2 5.8 7.3 8 8.8
DC OR STORED ENERGY (VDC) <27 30 48 110 300 600 1000