3305548

RIT SK RTT BLUE E WALL MNT COOLER 1500W


3305548

Description
Energy-efficient Blue e wall-mounted cooling units with e-Comfort controller, RiNano coating on the condenser and electrical condensate evaporation integrated as standard, protection class UL Type 3R/4, 12.
Benefits
Suitable for outdoor installation Blue e technology May be linked to the IoT interface via the Blue e IoT adaptor
Material
Carbon steel
Color
RAL 7035
Protection category IP to IEC 60 529
External circuit, IP 34 Internal circuit IP 56
Protection category NEMA
with standard filter: UL Type 3R with standard filter: UL Type 4 with standard filter: UL Type 12
Supply includes
Nano-coated condenser Wired ready for connection (plug-in terminal strip) Drilling template Fasteners Integral electric condensate evaporation
Note
Compressor cooling mode from +10?°C ambient temperature. Only the internal fan is active in the temperature range -20?°C to +10?°C.
Variant
wall-mounted
Total cooling output to DIN EN 14511
L 35 L 35 at 50 Hz: 1.49 kW L 35 L 35 at 60 Hz: 1.7 kW L 35 L 50 at 50 Hz: 1.04 kW L 35 L 50 at 60 Hz: 1.17 kW
Air throughput (unimpeded air flow)
External circuit: 950 m?/h Internal circuit: 540 m?/h
Rated operating voltage
400?V, 3~, 50?Hz 460?V, 3~, 60?Hz
Dimensions
Height: 1020 mm Width: 405 mm Depth: 358 mm
Temperature control
e-Comfort Controller (factory setting +35?°C)
Installation depth
410 mm (16″)
Temperature range
Storage: -40?°C...+70?°C Operation (environment): -20?°C...+50?°C Setting range: +20?°C...+50?°C
Refrigerant/cooling medium
Refrigerant: R134a Quantity: 500 g Global Warming Potential (GWP): 1430 CO? equivalent (CO?e): 0.72 t
Rated power Pel
L 35 L 35 at 50 Hz: 0.65 kW L 35 L 35 at 60 Hz: 0.82 kW L 35 L 50 at 50 Hz: 0.78 kW L 35 L 50 at 60 Hz: 0.96 kW
Rated current max.
At 50 Hz: 2.5 A At 60 Hz: 2.8 A
Start-up current (max.)
At 50 Hz: 12.2 A At 60 Hz: 11.3 A
Pre-fuse
Motor circuit-breaker: 6,3?A...10?A
Packaging unit
1 pc(s).
Weight/packaging unit
52 kg